盲板厚度与压力对照表【一览表】
盲板厚度计算表
钢管规格 | 压力等级 | 盲板厚度 | 钢管规格 | 压力等级 | 盲板厚度 |
Φ89×4 | ≤0.6 MPa | ≥8.0㎜ | Φ325×8 | ≤0.6 MPa | ≥16.0㎜ |
≤1.0 MPa | ≥10.0㎜ | ≤1.0 MPa | ≥20.0㎜ | ||
≤1.6 MPa | ≥12.0㎜ | ≤1.6 MPa | ≥24.0㎜ | ||
≤2.5 MPa | ≥14.0㎜ | ≤2.5 MPa | ≥28.0㎜ | ||
Φ108×4 | ≤0.6 MPa | ≥10.0㎜ | Φ377×10 | ≤0.6 MPa | ≥18.0㎜ |
≤1.0 MPa | ≥10.0㎜ | ≤1.0 MPa | ≥22.0㎜ | ||
≤1.6 MPa | ≥12.0㎜ | ≤1.6 MPa | ≥28.0㎜ | ||
≤2.5 MPa | ≥14.0㎜ | ≤2.5 MPa | ≥32.0㎜ | ||
Φ133×4.5 | ≤0.6 MPa | ≥10.0㎜ | Φ426×10 | ≤0.6 MPa | ≥20.0㎜ |
≤1.0 MPa | ≥12.0㎜ | ≤1.0 MPa | ≥26.0㎜ | ||
≤1.6 MPa | ≥14.0㎜ | ≤1.6 MPa | ≥30.0㎜ | ||
≤2.5 MPa | ≥16.0㎜ | ≤2.5 MPa | ≥36.0㎜ | ||
Φ159×4.5 | ≤0.6 MPa | ≥12.0㎜ | Φ530×12 | ≤0.6 MPa | ≥24.0㎜ |
≤1.0 MPa | ≥14.0㎜ | ≤1.0 MPa | ≥30.0㎜ | ||
≤1.6 MPa | ≥16.0㎜ | ≤1.6 MPa | ≥36.0㎜ | ||
≤2.5 MPa | ≥18.0㎜ | ≤2.5 MPa | ≥44.0㎜ | ||
Φ219×7 | ≤0.6 MPa | ≥14.0㎜ | Φ630×12 | ≤0.6 MPa | ≥28.0㎜ |
≤1.0 MPa | ≥16.0㎜ | ≤1.0 MPa | ≥34.0㎜ | ||
≤1.6 MPa | ≥18.0㎜ | ≤1.6 MPa | ≥42.0㎜ | ||
≤2.5 MPa | ≥22.0㎜ | ≤2.5 MPa | ≥52.0㎜ | ||
Φ273×8 | ≤0.6 MPa | ≥14.0㎜ |
|
|
|
≤1.0 MPa | ≥18.0㎜ |
|
|
| |
≤1.6 MPa | ≥22.0㎜ |
|
|
| |
≤2.5 MPa | ≥24.0㎜ |
|
|
|
注:以上材质均为16MnR,且温度不高于150℃时算得,若高于150℃则需经压检站重新核算。以上盲板皆为焊接。
法兰盲板照样可以用法兰连接方式,即垫片放在两法兰密封面之间,拧紧螺母后,垫片表面上的比压达到一定数值后产生变形,并填满密封面上凹凸不平处,使连接严密不漏,但是,不同压力的法兰盲板有不同的厚度和使用不同的螺栓;在油类介质系统时,法兰盲板不需要做镀锌处理,但用于其他介质系统时,法兰盲板应经过热镀锌处理,最小浸锌层重量610g/m2,热浸锌后的法兰盲板质量应按国家标准进行检验。